We ran the same window two ways. First on its own, the way it is tested for a rating — the window and its timber reveal, outside air on the outer face only, the underside treated as insulated. Then installed, set into a 400 mm slice of a real timber-framed wall: cladding, a ventilated cavity, a wall wrap, insulation and plasterboard. Same window, same glass. Two very different results.
Both are the windows from Episode 2 — Window B, aluminium with a polyamide thermal break; Window A, the same frame with no break. One definition carries the whole episode: a thermal bridge is a single piece of metal that touches both room air and outside air at once. A thermal break exists to cut that path.
On paper, the break works
Tested on its own, Window B has no thermal bridge. The polyamide break severs the metal path, so no single piece of aluminium runs from room to outside; the easiest route for heat is through the warm-edge spacer at the glass, not the frame. The coldest room-side surface sits at 13.1 °C — above the mould line (12.6 °C) and clear of the condensation line (9.3 °C). Nothing on the room side gets wet. The break is doing exactly what it is sold to do.
Install it, and the cavity becomes the bridge
Now set the same window into the wall. Beneath the frame is the ventilated cavity behind the cladding — and under ISO 6946 that cavity sits at outside-air temperature, because it is open to outside air to drain and dry. The room-side metal of the frame now reaches that cavity: a single piece of aluminium touches room air on one face and, through the cavity, outside air on the other. The bridge the break removed has reappeared — not through the break, but around it.
The coldest room-side surface drops to 10.2 °C, into the mould-risk band, and the mould line swings up onto the room-side frame face and the glazing-bead-to-reveal junction. No bridge on paper; the ventilated cavity is the new bridge once it is installed.
Installed, Window B’s metal route reads R 0.159 m²K/W — two surface air films and nothing else. That is exactly the figure for the window with no thermal break at all. The break is bypassed, not weakened.
Aluminium adds almost no resistance, so the moment there is any continuous metal route from room to cavity, the frame conducts as if the break were never there. You paid for the break; the install gave it back.
A conduction fix for a convection problem
Here is the deeper reason it happens. A thermal break is a conduction fix — resistance inserted into the solid metal to slow heat conducted through the frame. But the installed failure is convection: the ventilated cavity sweeps outdoor air against the back of the frame and holds it at outside temperature (which is why ISO 6946 counts a well-ventilated cavity as outside air). A conduction fix can’t touch a convection problem — it was aimed at the wrong mechanism. The cavity keeps delivering the cold; the metal keeps conducting it inward, around the break.
The window with no break — worse either way
For contrast, Window A (no break) is bridged in both models. On its own, its coldest surface is already 9.6 °C, in the mould band. Installed, it falls to 8.3 °C — below the condensation line: the room-side surface doesn’t just risk mould, it collects water. The break still helps — B runs a couple of degrees warmer than A — but the install cancels the headline benefit the break was bought for.
I’ve been on about this for years, from commercial framing and the drainage slots in sub-sills — the room-side metal quietly seeing outside air through the cavity. What the modelling adds is that you can now see it: on paper there is no bridge; installed, the cavity is the bridge. The break is real — it just has to sit where the wall is warm, not hung out over open cavity.
Don’t blame the ventilation
The cavity is meant to be ventilated. The NCC asks for openings of at least 1,000 mm² per metre at the base and top of a wall cavity so it can drain and dry — that keeps the wall healthy, and it is not up for debate. The fix is never to seal the cavity up. It is to stop the room-side skin of the frame sitting bare to it — to insulate the junction so the break is in the warm plane, not stranded in outside air. How much insulation that takes, and where, is the next episode.
Common questions
Does a thermal break stop condensation?
On its own, yes — in this model the broken window’s coldest room-side surface stays at 13.1 °C, above both the mould and condensation lines. But that is the window tested alone. Once it is installed over a ventilated cavity, the room-side metal reaches outside air through the cavity, the coldest surface drops to 10.2 °C, and the mould line moves onto the frame.
What is a thermal bridge, exactly?
A single piece of material — usually metal — that touches both room air and outside air at once, giving heat a continuous path from warm to cold. A thermal break interrupts that path; the catch in this episode is that the installation can hand the metal a new path around the break, through the ventilated cavity.
Why does the installed broken window read the same as one with no break?
Because aluminium barely resists heat. Once any continuous metal route exists from the room to the cavity, the resistance is just the two surface air films — about R 0.159 m²K/W — whether or not there is a break further along the frame. The break is bypassed, not weakened.
So is a thermal break still worth it?
Yes. The break is genuinely better than no break — here it keeps the room-side surface a couple of degrees warmer than the unbroken window, which drops below the dew point. The point is that its benefit depends on where it sits once installed, so the frame should be modelled as built, not taken from a catalogue figure.
My new windows are already sweating — what do I do?
If the home is built and the windows run with water or grow mould, the cause is usually a cold junction, not a faulty window. An independent window audit models what you actually have as installed and shows what will fix it.
Is your break in the warm plane, or stranded over the cavity?
Send us one window and the opening it goes into. We’ll model the frame where it actually sits — cavity and all — and show you whether the break survives the installation or gets bypassed by it, before it is built.
Send us one window →Modelled results, indicative to the sections, climate and conditions described. Steady-state 2-D analysis to ISO 15099 (AFRC Lab’s Computational Façade Lab), on a TIRS climate-zone-5 (Sydney) winter design day: outside 7.2 °C, room 20 °C at 50 % RH, condensation line 9.3 °C, mould line 12.6 °C. Design-day snapshots for one wall and one climate zone, not a compliance report; the sections are generic illustrations, not a specific product. Whole-of-year mould results and how much insulation the gap needs are the next episode. AFRC Lab (Advanced Fenestration Research & Certification) is an independent consultancy; it is not the AFRC. TIRS™ and the CFL (Computational Façade Lab) engine are of AFRC Lab Pty Ltd.