AFRC Lab Window-to-wall explorer

Window-to-wall insights · 160 details · 10 years, 2015 to 2024 · NCC climate zones 1 to 8

What 160 window-to-wall details tell us about mould

81 of 160 modelled window-to-wall details stay below the NCC mould limit over 10 years of real weather. The window frame type and the gap seal decide most of the outcome, and the climate zone decides how much margin you have.

A further 80 details in CZ1, CZ2, CZ5 and CZ6 are being re-run on KD treated pine framing. They are added, and these findings recalculated, automatically as each one finishes.

1. How many details stay below the limit, by climate zone

Every combination of window, gap seal and orientation in each zone. The least margin is in CZ8 Thredbo, CZ7 Canberra, CZ2 Brisbane; the most in CZ3 Alice Springs.

CZ1
Darwin
CZ2
Brisbane
CZ3
Alice Springs
CZ4
Mildura
CZ5
Sydney
CZ6
Melbourne
CZ7
Canberra
CZ8
Thredbo
Details below the limit10/109/1020/3010/309/109/108/306/30

2. Which gap seals stay below the limit, and where

Counts across all three window types, north and south. Click any cell to open that zone and gap seal in the explorer. Most details below the limit overall: Vapour-open tape, gap left empty and Vapour-open tape, 20 mm Hanno Band BG1 pre-compressed foam tape and Vapour-open tape, full-depth Hanno Band BG1 pre-compressed foam tape (18 of 28 each).

Gap sealCZ1
Darwin
CZ2
Brisbane
CZ3
Alice Springs
CZ4
Mildura
CZ5
Sydney
CZ6
Melbourne
CZ7
Canberra
CZ8
Thredbo
Closed-cell tape, gap left empty1/11/14/62/61/11/11/60/6
Vapour-open tape, gap left empty2/22/24/62/62/22/22/62/6
Vapour-open tape, 20 mm Hanno Band BG1 pre-compressed foam tape2/22/24/62/62/22/22/62/6
Vapour-open tape, full-depth Hanno Band BG1 pre-compressed foam tape2/22/24/62/62/22/22/62/6
Closed-cell tape, full PU foam3/32/34/62/62/32/31/60/6

3. The part of the junction that governs, by window type

For each detail, which part reaches the highest mould index: the window frame and sill surfaces, the gap between window and wall, or the wall around the opening. Bold is the most common.

WindowWindow partGapWall
Aluminium window, no thermal break40 of 40
median peak 5.29
0 of 40
median peak 0.54
0 of 40
median peak 0.70
Thermally broken aluminium window43 of 44
median peak 5.27
0 of 44
median peak 0.56
1 of 44
median peak 0.80
uPVC window0 of 76
median peak 0.05
32 of 76
median peak 0.51
44 of 76
median peak 1.01

4. How much the thermal break helps

The same gap seal, zone and orientation with and without a thermal break in the aluminium frame. Adding the thermal break turns 10 of 40 details from exceeding to staying below the limit (0 go the other way), and lowers the window-part peak by a median of 0.01.

ZoneAluminium, no thermal breakThermally broken aluminium
CZ1 Darwin0/00/0
CZ2 Brisbane0/00/0
CZ3 Alice Springs0/1010/10
CZ4 Mildura0/100/10
CZ5 Sydney0/00/0
CZ6 Melbourne0/00/0
CZ7 Canberra0/100/10
CZ8 Thredbo0/100/10

5. uPVC and aluminium windows, zone by zone

Details below the limit for each window type (five gap seals, north and south). Overall: Aluminium window, no thermal break 0 of 40; Thermally broken aluminium window 11 of 44; uPVC window 70 of 76.

WindowCZ1
Darwin
CZ2
Brisbane
CZ3
Alice Springs
CZ4
Mildura
CZ5
Sydney
CZ6
Melbourne
CZ7
Canberra
CZ8
Thredbo
Aluminium window, no thermal break0/00/00/100/100/00/00/100/10
Thermally broken aluminium window1/10/110/100/100/10/10/100/10
uPVC window9/99/910/1010/109/99/98/106/10

6. North versus south

North-facing details stay below the limit in 39 of 76 cases, south-facing in 42 of 84. Across these details orientation makes little difference to the verdict: the window frame and gap seal matter far more.

Check your own detail

Pick your zone, window and gap seal in the explorer, or have your own section modelled for your project.

Indicative design guidance for generic details, not a compliance certificate or a project verification. AIRAH DA07 mould index against the NCC F8V1 / H4V5 limit of 3, 2-D hygrothermal simulation, 10 consecutive weather years per climate zone city. Timber frame (KD treated pine), glass wool, plasterboard, vapour-permeable wall wrap, fibre-cement cladding; generic windows with double glazed IGU (single-silver low-e #3). Materials are typical generic products, except Hanno Band BG1 pre-compressed foam tape. The hygrothermal engine is verified against the HAMSTAD and EN 15026 benchmarks: read the verification report.